Product details
| Protocol | USB, Ethernet, CAN Bus, RS232/RS485 |
| USB Interface | For TX7810 programming and TX7812 GMC server/client interface |
| Ethernet | Optional TCP/IP networking or email notification |
| CAN Bus | Network interface supporting up to 512 control panels with full monitoring |
| Serial Ports | RS232/RS485 for third-party system integration, optional Modbus RTU |
| Power & Cable Limits | USB: 15m, CAN Bus: 3km (2×1.5mm²), RS232: 15m, RS485: 1000m |
| Operating Environment | Temperature: -10℃ to +55℃, Humidity: ≤95% non-condensing |
| Ordering Variants | NC7004, NC7004-Modbus, NC7004-IP supporting Modbus RTU or TCP/IP Networking |
Description
The NC7004 Network Communication Card by TANDA UK Ltd is a versatile communication solution designed for TX7 series control panels. It integrates multiple protocols including USB, Ethernet, CAN Bus, and RS485/RS232, allowing seamless connectivity with third-party systems and devices. The USB interface supports programming the control panel and interfacing with the Graphic Monitor Center (TX7812). The CAN Bus network can monitor and control up to 512 control panels, with full transmission path monitoring to detect faults. The Ethernet port enables IP networking and email notifications, enhancing remote communication capabilities. RS485/RS232 connectivity allows integration with building management systems or other third-party devices. The card is panel-mounted with plug-in terminals for easy installation and requires no specific positioning or addressing. Additionally, the NC7004 is compatible with optional Modbus RTU and TCP/IP networking variants, ensuring flexible deployment in various network configurations. Its robust power and environmental ratings make it suitable for reliable operation in a wide range of conditions.
- The NC7004 Network Communication Card supports multiple protocols including USB, Ethernet, CAN Bus, and RS485/RS232, enabling flexible connectivity for TX7 series control panels.
- The USB interface allows programming the control panel and connecting to the Graphic Monitor Center (TX7812) server and client machines.
- CAN Bus networking supports up to 512 control panels in a single ring, with full transmission path monitoring to detect short circuits or open circuits.
- The Ethernet port enables TCP/IP networking and email notifications for enhanced remote communication and system alerts.
- RS485/RS232 ports facilitate integration with third-party systems such as building management systems, and optional Modbus RTU support is available.
- The card is panel-mounted, plug-in terminals are removable, and it requires no specific positioning or addressing, simplifying installation.
- Robust operational capabilities include USB cable lengths up to 15 meters, CAN Bus up to 3 km, RS232 up to 15 meters, RS485 up to 1000 meters, and environmental tolerance from -10℃ to +55℃ with humidity ≤95%.