| Model | TX7230 |
| Approval | LPCB / CE-CPR |
| Input Voltage | 24VDC [16V to 28V] |
| Current Consumption | Standby: 0.15mA, Alarm: 1.8mA |
| Protocol | T&A |
| Number of Monitored Devices | Maximum up to 70 Devices |
| Output Impedance | 480 ohms |
| Indicator Status | Normal: Single Blink / Active: Steady-On |
| Material / Color | ABS / White Glossy Finishing |
| Dimensions (L × W × H) | 108 × 86 × 38 mm |
| Weight | 152g (with Base), 81g (without Base) |
| Ingress Protection Rating | IP30 |
| Humidity | 0 to 95% RH, Non-Condensing |
Description
The TX7230 Analogue Addressable Isolator Module is a critical safety component designed to maintain the integrity of an addressable fire alarm loop. Its primary role is to automatically isolate short-circuited sections of the loop, ensuring that unaffected devices continue to operate without disruption. Built to EN54-17 standards, the TX7230 enhances system reliability by minimizing downtime and preventing a single fault from disabling the entire loop. With loop-powered operation, automatic reset functionality, and the ability to monitor up to 70 devices, it offers dependable performance and easy installation for indoor fire detection systems.
- EN54-17:2005 certified for reliable short-circuit isolation in addressable fire alarm systems.
- Automatically isolates faulty loop sections during a short circuit, protecting healthy devices.
- Self-resetting mechanism restores normal operation once the fault is cleared.
- Capable of monitoring up to 70 devices, reducing the need for multiple isolators.
- Integrated LED indicator provides clear visual status for normal and active conditions.
- Loop-powered design eliminates the need for an external power supply.
- Surface-mount installation with a fixed base allows quick and simple setup.